Step voltage and potential equalization

 

Step voltage and potential equalizationMany of us from childhood remember that a bare tattered wire that fell to the ground is very dangerous. I remember various passions-muzzles about wet weather and about unfortunate victims who did not even have “happiness” to touch the metal, which was energized and caused their injury. All in all, they managed to pass in dangerously close to the damaged line - and this was more than enough.

But what kind of phenomenon is it, thanks to which a wire that lies “innocently” lying to one side becomes a deadly threat? Everyone knows that an electric shock to a person can only be caused by an electric current passing through his body. And electric current needs a clear path. At least two points of application on the body of the unlucky one are necessary: ​​one of them is the phase from where the current can come, and the second is zero, where it can freely go.

But excuse me, what is the “phase"? Well, “zero” is still understandable, but where does the “phase” come from, if a person calmly walks on the ground and doesn’t even touch any wires? It seems that there is nothing like that - it’s just wet ground. A path, for example. Well, yes, the phase ragged wire lies nearby in the bushes. But he closed himself directly to the ground - the circuit does not include a pedestrian walking and the current should not go through it. But it only seems so.

There would be nothing to fear if the earth was an excellent conductor with a resistance close to that of a metal. Then a wire break and its fall to the ground would end with a banal short circuit.

The overcurrent protection would work, or the torn wire would burn, but in any case, this would not last long. But in reality, the electrical resistivity of the soil is at least 60 Ohm * m, and most often more, even if the weather is wet and it is raining. Therefore, when the cause breaks and it is shorted to ground for electric current, a new circuit simply arises: a phase wire - ground - a grounded neutral of the transformer.

Due to the not very high conductivity of the earth, the current has to work hard to get through this circuit, but it has no options. The current “would gladly take advantage” of some other, “parallel road,” which would allow him to shorten the path. And the pedestrian’s body can become so expensive.

Speaking scientifically, on the only significant resistance of the wire-ground-neutral circuit - wet soil - there is a voltage drop (change in electrical potential) from 220 volts near the fallen wire to zero at the transformer neutral.

 

Step voltage

This fall occurs non-linearly, but the point is that the closer to the wire, the more rapidly the potential of the earth increases. This means that the closer to the cliff point, the greater the potential difference between two surface points located at a certain distance. And an unfortunate passer-by can stand with one foot on the first of these points and with the other foot on the second of them. In this case, of course, he will take on the potential difference that has arisen, and this can turn out to be almost all phase voltage if the wire is close.

Of course, where the voltage appeared, the current there will not keep itself waiting. That's all. Not having time to realize the severity of his situation, a passerby receives an electric shock, possibly fatal.

The tension that occurs in such cases between the feet of a person is called "Step voltage" or “step tension,” and there are some measures to deal with it.

Step voltage and potential equalization

The most reliable of these measures is potential equalization. At the same time, the surface area of ​​the soil, where an accident with a phase fault to the ground is possible, is equipped with a grid of grounded conductors laid directly below the surface.

It works very simply: the potential of the conductor at all points is always the same, so being on such a grid is simply impossible to get under voltage. Equalization of potentials is carried out on the territory of open switchgears (outdoor switchgear) and in other potentially dangerous places.

But, unfortunately, it is impossible to equip each transmission line support with a potential equalization grid. Therefore, every person who is not even an electrician needs to be vigilant: pay attention to the condition of power lines around you, especially in rainy weather. Pay attention to your feelings: if you are “pinched,” or even “shaken,” when walking, this is a fairly sure sign of the effect of step voltage.

Having understood that you are in the zone of possible impact of step voltage, you need to try to get out of it. But this must be done with a goose step - placing the heel of the foot that you are walking on to the toe of the foot on which you are standing. Thus, when walking, both legs will be practically at the same point with one electric potential - there will be no voltage between them.

You can also "jump" on one leg, if you are sure that you will succeed. You should not rush - you can stumble, fall on your hands and fall under the greatest possible tension that arises between two remote points.

See also at bgv.electricianexp.com:

  • What is touch voltage?
  • Resistance of the human body - what it depends on and how it can change
  • Thunderstorm and lightning: what you need to know about it
  • Equalization Systems
  • Networks up to and above 1000 volts. What are the differences?

  •  
     
    Comments:

    # 1 wrote: Kristina | [quote]

     
     

    But we cannot always find out if there is any wire with voltage at a given distance.
    You never know, it rains outside, we go suspecting nothing, somewhere in the bushes the wire is rippling, but we don’t know anything, suddenly when you write you “pinch”, or even “shake” when walking, it’s easy for someone to seem so, and no one can even suspect that this could be dangerous.
    But I didn’t understand why you can’t run, but just go with a goose step?

     
    Comments:

    # 2 wrote: Author | [quote]

     
     

    Christina, dear, of course, it is my fault that you did not understand the danger of step voltage and how it arises. Without a shadow of irony. I'll think about how it can be described more simply and unsubscribe to you here. Have you agreed?

    In general, the situation is this: if you walk freely and freely along the current spreading zone (the zone of influence of the step voltage), then the electric current has the opportunity to go from point A to point B through your body: first one foot and then the other . Of course, the current will certainly take this opportunity. This is for him like a bypass road around the city - maybe there will be less traffic jams. From the part of the current that took the bypass, you get hit.

    The more distant points you connect with your feet, the more electrons will want to take a detour and the stronger the blow.

    If you go with a goose step, your legs are almost at one point. What is the use of current to take a detour that leads them to the same point?

    And about the fact that it is not easy to notice a damaged line and understand that you are in danger, this is so, there is nothing to be done. You have to be careful.

     
    Comments:

    # 3 wrote: | [quote]

     
     

    But if I run, but so that one of the legs always remains a canopy? In general, jump from foot to foot ...

     
    Comments:

    # 4 wrote: Author | [quote]

     
     

    Igor: you will stumble most likely. The result will be a little predictable.

     
    Comments:

    # 5 wrote: | [quote]

     
     

    It is strictly forbidden to engage in amateur activity when leaving the zone of action of step voltage (jumping on one leg, running “canopy”, “flying”, etc.). Since in the fall of 100% of you will remain "cracklings."

    When leaving the zone of step voltage, it is necessary to do this as carefully as possible, albeit slowly, without taking your legs apart, and not try to leave the dangerous place as quickly as possible.

    From experience, I once observed a terrible picture when a dog fell under a stepper, on a cliff of a 35 kV line. And I’ll tell you when I wrote above about cracklings I did not ironize.

     
    Comments:

    # 6 wrote: Andrew | [quote]

     
     

    It is not clear why step voltage occurs. After all, if the wire falls to the ground, then this is a short circuit and the voltage on the wire should be turned off by the protection at the substation. It turns out that it may not turn off? This is if the parameters of the protection devices are not correctly selected? How often does this happen? It seems to me that in modern conditions, step voltage due to wires on the ground is a very rare occurrence.

     
    Comments:

    # 7 wrote: andy78 | [quote]

     
     

    When a wire falls in networks with an insulated transformer neutral (6-35 kV), not a short circuit occurs, but a single-phase earth fault with small currents. The magnitude of these currents is not enough to turn off the protection devices. Accordingly, the line does not turn off. Hence the danger of falling under step voltage. Possible reasons for the occurrence of step voltage during wire breakage in networks with a 0.4 eV neutral earthed neutral are described in the article.

     
    Comments:

    # 8 wrote: | [quote]

     
     

    I was not interested in this issue in the PUE, however, we have our own instruction that when such a wire is detected, you can’t get closer to it closer than 8 meters in open areas .... although I think this is a pretty conditional security parameter. It’s better for all ignorant people to walk from power lines for about 30 meters. From harm's way. Yes, and a short to ground can be stable not only from a fallen wire, but simply through the power line support. There is generally nothing to notice unfortunately.

     
    Comments:

    # 9 wrote: | [quote]

     
     

    SAY PLEASE, IF IF I HAVE A 220 VOLT CABLE FROM HOME TO THE BAR IN EARTH AND IF IT WILL BE DAMAGED, MAY ALSO BE KILLED BY ELECTRIC SHOCK OR THE AUTOMATIC POWER OFF? THANKS.

     
    Comments:

    # 10 wrote: Author | [quote]

     
     

    Petro, you can’t say for sure. You need to know the rating of the machine and the characteristics of the soil. But most likely, the situation described in the article will arise.

     
    Comments:

    # 11 wrote: | [quote]

     
     

    a new circuit arises: phase wire - earth - grounded neutral of the transformer.

    I’m not an electrician, I can’t understand at all: where the hell of her daughter, in the earth, on which the phase conductor fell, will also take the grounded neutral of the transformer? Explain in more detail, if not difficult.

     
    Comments:

    # 12 wrote: Author | [quote]

     
     

    Anonymous:

    The neutral of the transformer is EARTHED, meaning "CONNECTED TO EARTH". But we have one land for all: that’s the result.

     
    Comments:

    # 13 wrote: Anonymous | [quote]

     
     

    Again, a stupid question, but: that is, it turns out that the current right here on this earth reaches the neutral of the transformer? And if it is hundreds of thousands of kilometers?

    Although I still seemed to delve into the essence. Around the fallen wire in the danger zone, each point receives a certain potential. As you move away from the cliff point, the potential will decrease, and where there is a potential difference, there is voltage. Accordingly, the closer one of our legs to the precipice and the further the other, the greater the potential difference, respectively, the greater the voltage. It’s the same as plugging yourself in with two legs :)

     
    Comments:

    # 14 wrote: Author | [quote]

     
     

    In the gap between the fallen wire and the distant neutral of the transformer, there are a number of repeated groundings: on the input devices, on the supports, everywhere. Through each such grounding, the current already quite freely reaches neutral by wire.

     
    Comments:

    # 15 wrote: Anonymous | [quote]

     
     

    Author, wow, I never knew about anything like that. Thanks.

     
    Comments:

    # 16 wrote: sasha | [quote]

     
     

    What is killing? 0.1 or 1000?

     
    Comments:

    # 17 wrote: | [quote]

     
     

    Hello everybody.You ask what kills - kills power. A weak current and high voltage will not kill you, it will only scare you. If you had to try the candle wire on a motorcycle or car, then this is exactly the situation. The power we have is the current times the voltage. If we have a weak current multiplied by a high voltage, then we get a weak power as a result. Lethal current is considered 0.1 amperes at a voltage of 220 volts. Not so much 22 watts, but fatal. There is a lot of voltage on the car’s candle - 22,000 volts, but a very, very weak current, the power, although not fatal, still hits hard. With fright it can become bad .. I also want to add a step voltage on the topic. Namely, the grounded neutral of the transformer. This is not done smartly from a security point of view. With the transformer neutral grounded, people already walk on this danger and only has to touch the phase somewhere and the person is already shocking even if this touch is obtained not by direct touch, but through wet ground or a wet tree. Earthed neutral was invented in order to save ALUMINUM WIRE. In this case, part of the current goes through the earth, and part goes through a grounded thin zero wire. And how many thousands of human lives cost such savings in ALUMINUM WIRE. And then they say that you need a good grounding to protect against electric shock, and what protection if a person already walks through a wire under voltage called EARTH. In many countries, it has long been abandoned by a grounded neutral. In our age, there are many other ways to make electricity safe and without an EARTHED NEUTRAL TRANSFORMER. I wish you all the best! Peter.

     
    Comments:

    # 18 wrote: | [quote]

     
     

    And if the cable fell into the water, what to do then? Water, let’s say, waist-deep, like on a street crowded after heavy rain. How to survive?